Beijer-electronics BFI-P2 V1.21 Manual do Utilizador Página 37

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 36
UserGuideRevision1.121
www.beijerelectronics.com
37
8. ExtendedParameters
8.1. ParameterGroup2‐Extendedparameters
Par ParameterName Minimum Maximum Default Units
P201 Preset/JogFrequency/Speed1 P102 P101 5.0 Hz/Rpm
P202 Preset/JogFrequency/Speed2 P102 P101 10.0 Hz/Rpm
P203 Preset/JogFrequency/Speed3 P102 P101 25.0 Hz/Rpm
P204 Preset/JogFrequency/Speed4 P102 P101 50.0(60.0) Hz/Rpm
P205 Preset/JogFrequency/Speed5 P102 P101 0.0 Hz/Rpm
P206 Preset/JogFrequency/Speed6 P102 P101 0.0 Hz/Rpm
P207 Preset/JogFrequency/Speed7 P102 P101 0.0 Hz/Rpm
P208 Preset/JogFrequency/Speed8 P102 P101 0.0 Hz/Rpm
PresetSpeeds/FrequenciesselectedbydigitalinputsdependingonthesettingofP113.
IfP110=0,thevaluesareenteredasHz.IfP110>0,thevaluesareenteredasRpm.
Settinganegativevaluewillreversethedirectionofmotorrotation.
P209 SkipFrequencyCentrePoint P102 P101 0.0 Hz/Rpm
P210 SkipFrequencyBandWidth 0.0 P101 0.0 Hz/Rpm
TheSkipFrequencyfunctionisusedtoavoidtheDriveoperatingatacertainoutputfrequency,forexampleatafrequencywhich
causesmechanicalresonanceinaparticularmachine.ParameterP209definesthecentrepointoftheskipfrequencyband,andis
usedconjunctionwithP210.TheDriveoutput
frequencywillrampthroughthedefinedbandattheratessetinP103andP104
respectively,andwillnotholdanyoutputfrequencywithinthedefinedband.Ifthefrequencyreferenceappliedtothedriveis
withintheband,theDriveoutputfrequencywillremainattheupper
orlowerlimitoftheband.
P211 AnalogOutput1(Terminal8)FunctionSelect 0 11 8 ‐
DigitalOutputMode.Logic1=+24VDC
0:DriveEnabled(Running).Logic1whentheDriveisenabled(Running)
1:DriveHealthy.Logic1WhennoFaultconditionexistsonthedrive
2:AtTargetFrequency(Speed).Logic1whentheoutputfrequencymatchesthesetpointfrequency
3:OutputFrequency>0.0.Logic1whenthemotorrunsabovezerospeed
4:OutputFrequency>=Limit.Logic1whenthemotorspeedexceedstheadjustablelimit
5:OutputCurrent>=Limit.Logic1whenthemotorcurrentexceedstheadjustablelimit
6:MotorTorque>=Limit.Logicwhenthemotortorqueexceedstheadjustablelimit
7:AnalogInput2SignalLevel>=Limit.LogicwhenthesignalappliedtotheAnalogInput2exceedstheadjustablelimit
Note:Whenusingsettings47,parametersP216andP217
mustbeusedtogethertocontrolthebehaviour.Theoutputwill
switchtoLogic1whentheselectedsignalexceedsthevalueprogrammedinP216,andreturntoLogic0whenthesignalfallsbelow
thevalueprogrammedinP217.
AnalogOutputMode
8:OutputFrequency(MotorSpeed).0toP01
9:Output(Motor)Current.0to200%ofP108
10:MotorTorque.0to200%ofmotorratedtorque
11:Output(Motor)Power.0to150%ofdriveratedpower
P212 AnalogOutput1(Terminal8)Format SeeBelow
U 0-10
‐
U 0-10 =0to10V.
U 10-0=10to0V,
A 0-20=0to20mA
A 20-0=20to0mA
A 4-20
=4to20mA
A 20-4=20to4mA
P213 AnalogOutput2(Terminal11)FunctionSelect 0 11 9‐
DigitalOutputMode.Logic1=+24VDC
0:DriveEnabled(Running).Logic1whentheDriveisenabled(Running)
1:DriveHealthy.Logic1WhennoFaultconditionexistsonthedrive
2:AtTargetFrequency(Speed).Logic1whentheoutputfrequencymatchesthesetpointfrequency
3:OutputFrequency>0.0.Logic1whenthemotorrunsabovezerospeed
4:OutputFrequency>=Limit.Logic1whenthemotorspeedexceedstheadjustablelimit
5:OutputCurrent>=Limit.Logic1whenthemotorcurrentexceedstheadjustablelimit
6:OutputToque>=Limit.Logicwhenthemotortorqueexceedstheadjustablelimit
7:AnalogInput2SignalLevel>=Limit.LogicwhenthesignalappliedtotheAnalogInput2exceedstheadjustablelimit
Note:Whenusingsettings47,parametersP216andP217
mustbeusedtogethertocontrolthebehaviour.Theoutputwill
switchtoLogic1whentheselectedsignalexceedsthevalueinP216,andreturntoLogic0whenthesignalfallsbelowinP217.
AnalogOutputMode
8:OutputFrequency(MotorSpeed).0toP01
9:Output(Motor)Current.0to200%ofP108
10:MotorTorque.0to200%ofmotorratedtorque
11:Output(Motor)Power.0to150%ofdriveratedpower