P1‐11 V/FModeVoltageBoost 0.0 DriveRatingDependent %
Voltageboostisusedtoincreasetheappliedmotorvoltageatlowoutputfrequencies,inordertoimprovelowspeedandstarting
torque.Excessivevoltageboostlevelsmayresultinincreasedmotorcurrentandtemperature,andforceventilation ofthemotormay
berequired.
Anautomaticsetting(Auto)isalso
possible,wherebytheDrivewillautomaticallyadjustthisparameterbasedonthemotor
parametersmeasuredduringanautotune.
P1‐12 PrimaryCommandSourceMode 0 6 0 ‐
0:TerminalControl.Thedriverespondsdirectlytosignalsappliedtothecontrolterminals.
1:Uni‐directionalKeypadControl.ThedrivecanbecontrolledintheforwarddirectiononlyusinganexternalorremoteKeypad
2:Bi‐directionalKeypadControl.Thedrivecanbecontrolledintheforward andreversedirectionsusinganexternalorremote
Keypad.PressingthekeypadSTARTbuttontogglesbetweenforwardandreverse.
3:PIDControl.TheoutputfrequencyiscontrolledbytheinternalPIDcontroller.
4:FieldbusControl.ControlviaModbusRTUifnofieldbusinterfaceoptionispresent,otherwise controlisfromthe
fieldbusoption
moduleinterface
5:SlaveMode.ThedriveactsasaSlavetoaconnectedDriveoperatinginMasterMode
6:CANbusControl.ControlviaCANbusconnectedtotheRJ45serialinterfaceconnector
P1‐13 DigitalInputsFunctionSelect 0 21 1 ‐
Definesthefunctionofthedigitalinputsdependingonthecontrolmodesettingin
P1‐12.Seesection7.1formoreinformation.
P1‐14 ExtendedMenuAccessCode 0 30000 0 ‐
ParameterAccessControl.Thefollowingsettingsareapplicable:
P1‐14=P2‐40=101:AllowsaccesstoParameterGroups0–5
P1‐14=P6‐30=201=Allowsaccesstoallparametergroups(Intendedforexperiencedusersonly,usageisnotdescribedinthisUser