Beijer-electronics BFI-P2 V1.21 Manual do Utilizador Página 15

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 14
UserGuideRevision1.121
www.beijerelectronics.com
15
3.7. Guidelinesformounting(IP55/IP66Units)
Beforemountingthedrive,ensurethatthechosenlocationmeetstheenvironmentalconditionrequirementsforthedriveshownin
section10.1
Thedrivemustbemountedvertically,onasuitableflatsurface
Theminimummountingclearancesasshowninthetablebelowmustbeobserved
Themounting
siteandchosenmountingsshouldbesufficienttosupporttheweightofthedrives
Drive
Size
X
Above&Below
Y
EitherSide
mm mm
2(IP66) 200 10
3(IP66) 200 10
4(IP55) 200 10
5(IP55) 200 10
6(IP55) 200 10
7(IP55) 200 10
Note:
Typicaldriveheatlossesare3%ofoperatingload
conditions.
Aboveareguidelinesonlyandtheoperatingambient
temperatureofthedriveMUSTbemaintainedatall
times.
CableGlandSizes
Drive
size
Power
Cable
Motor
Cable
Control
Cables
2 M25(PG21) M25(PG21) M20(PG13.5)
3 M25(PG21) M25(PG21) M20(PG13.5)
4 M32(PG29) M32(PG29) M20(PG13.5)
5 M50(PG36) M50(PG36) M20(PG13.5)
6and7 Nopredrilledglandholes
Usingthedriveasatemplate,orthedimensionsshownabove,markthelocationsrequiredfordrilling
SuitablecableglandstomaintaintheIPprotectionofthedrivearerequired.Glandsizesshouldbeselectedbasedonthenumberand
sizeoftherequiredconnectioncables.Drivesare
suppliedwitheitherpredrilledholesoraplain,undrilledglandplatetoallowthe
correctholesizestobecutasrequired.Removetheglandplatefromthedrivepriortodrilling.
X
X
Y Y
Vista de página 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 55 56

Comentários a estes Manuais

Sem comentários