Beijer-electronics iX Panel T100 EN Manual do Utilizador Página 12

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 46
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 11
Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincommunicationmay
occur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensationf orms,ensurethattheoperatorpanelisdrybeforeconnecting
ittothepoweroutlet.
Ensurethatthevol tageandpolarityofthepowersourceiscorrect.
Useonlyshieldedc ommunicationcables.
Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS422/RS485
24V DC
1
CF CARD
B
A
C
D
RS232
Controller
Power
Ethernet
Connect cable A.
Connect cable B, using an M5 screw and a groundin g conductor (as short
as possible) with a cross-section of minimum 2.5 mm
2
.
Connect cable C.
Connect cable D.
5.
Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
BeijerElectronics, MAEN007
12
Vista de página 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 45 46

Comentários a estes Manuais

Sem comentários